Modbus RTU

Modbus RTU uses a serial connection. Check addressing, framing and timing, then use the device's register map to interpret the returned values.

Sources and scopeSource record 25 August 2026

Technical source record: 25 August 2026. Check the linked documentation for current product requirements.

Electrical installation values and device timing limits must be taken from the current vendor manual and applicable cabling standard.

Verification and testing

Overview#

Modbus RTU places a unit address before the application PDU and a CRC-16 after it. Frame boundaries are derived from a silent interval, so baud rate, character format, receive buffering, and inter frame timing must be correct for frames to be interpreted reliably.1

text
address (1 octet) | function and data (PDU) | CRC low | CRC high

The public V1.02 guide is the baseline for new serial implementations; the specifications index labels the older 1996 serial document as legacy only.2

Receive state machine#

  1. Detect the start of a candidate frame after an idle boundary.
  2. Accumulate into a fixed maximum buffer while tracking timing.
  3. Determine completeness from the function specific shape and the next idle boundary.
  4. Validate address, length, and CRC before interpreting data.
  5. Correlate a response with exactly one outstanding request.
  6. Classify timeout, malformed frame, CRC failure, exception response, and valid response separately.

Don't resynchronise by scanning arbitrary bytes for a plausible address/function pair; that can turn line noise or a truncated frame into valid looking telemetry. Discard the bounded candidate at a framing violation and recover at a documented idle boundary.

Bus and gateway behaviour#

RTU is normally single request at a time on a multidrop serial segment. Enforce one bus owner and bounded turnaround. A TCP to RTU gateway multiplexes network clients onto this serialized resource; transaction IDs on the TCP side don't make the serial bus concurrent. Configure queue limits and per client fairness, and test what the gateway does on timeout, unit absence, broadcast, disconnect, and late replies.

Unit address 0 has broadcast semantics for supported write operations and receives no reply. Disable it unless the operational design explicitly requires it; an accidental broadcast write can affect every attached device.

Physical layer record#

Record the actual interface standard, two wire/four wire mode, baud, parity, stop bits, bias, termination, isolation, shield/ground practice, connector pinout, bus topology, and unit assignments. “RS485” alone isn't a complete interface contract. Use serial transports for electrical context.

Defensive controls#

  • Put serial servers and gateways in the OT trust zone; their web/management planes are separate exposure.
  • Allowlist expected unit IDs and read functions. Gate writes through explicit application authorisation and site interlocks.
  • Alert on CRC bursts, unexpected broadcasts, new talkers, write functions, and sustained timeout changes.
  • Use isolated taps for observation. Don't attach unterminated or incorrectly biased equipment to an operating bus.

Confirm CRC byte order, timing, and maximum ADU length against the normative guide before implementation.

Primary sources#